Boost, or amplify, RS-485 signals to cover longer distances with the PSM-ME-RS485 Repeater. By using differential voltage lines for data and control signalsRS-485 repeatersovercome the limitations of standard serial ports. This allows you to add 4,000 feet (1.2 km) and 32 nodes to an RS-485 data circuit. In addition, 3-way isolation protects devices from transient surges and ground loops on the data line.
The PSM-ME-RS485 repeater was developed for the high requirements of fieldbus systems. The device can be powered by wall-mount AC or snapped onto standard DIN rails and supplied with 24 V DC or AC.
The PSM-ME-RS485 repeater can be used in all common 2-wire bus systems: Modbus, RACKBUS (Endress &Hauser), SUBCONET-K (Moeller), UNI-TELWAY (Telemecanique), DANBUS (Danfoss), RS-BUS (Landis & Staefa), NET 2000 (B&R), INSUM (ABB), J-BUS (Merlin Gerin), ET-WAY (Jetter), S-BUS (SAIA) and around 60 more company-specific bus systems.
Boost, or amplify, RS-485 signals to cover longer distances with the PSM-ME-RS485 Repeater. By using differential voltage lines for data and control signalsRS-485 repeatersovercome the limitations of standard serial ports. This allows you to add 4,000 feet (1.2 km) and 32 nodes to an RS-485 data circuit. In addition, 3-way isolation protects devices from transient surges and ground loops on the data line.
The PSM-ME-RS485 repeater was developed for the high requirements of fieldbus systems. The device can be powered by wall-mount AC or snapped onto standard DIN rails and supplied with 24 V DC or AC.
The PSM-ME-RS485 repeater can be used in all common 2-wire bus systems: Modbus, RACKBUS (Endress &Hauser), SUBCONET-K (Moeller), UNI-TELWAY (Telemecanique), DANBUS (Danfoss), RS-BUS (Landis & Staefa), NET 2000 (B&R), INSUM (ABB), J-BUS (Merlin Gerin), ET-WAY (Jetter), S-BUS (SAIA) and around 60 more company-specific bus systems.
| Specifications | |
| 1 Year Return to Factory Warranty Reach, RoHS and WEEE Compliant HTSUS Number: 8517.62.0020 UNSPSC Code: 43222608 ECCN: 5A991 | |
| Serial interface | |
| Interface 1 RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wire | |
| Operating mode Semi-duplex | |
| Connection method Pluggable screw connection | |
| File format/coding UART (11/10 bit switchable; NRZ) | |
| Data direction switching Automatic control, min. station response time 1 bits | |
| Transmission medium 2-wire twisted pair, shielded | |
| Transmission length ≤ 1200 m (depends on transmission speed, bus system and cable type) | |
| Cascadability 9 (4,8 ... 93,75 kbps) 8 (115.2 kbps) 7 (136 kbps) 6 (187.5 kbps) 5 (375 ... 1500 kbps) | |
| Termination resistor 390 Ω 180 Ω 390 Ω (Can be connected) | |
| Conductor cross section flexible min. 0.2 mm² | |
| Conductor cross section flexible max. 2.5 mm² | |
| Conductor cross section AWG min. 24 | |
| Conductor cross section AWG max. 12 | |
| Protocols supported transparent protocol | |
| Serial transmission speed 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 75 / 93.75 / 115.2 / 136 / 187.5 / 375 / 500 / 1500 kbps | |
| Interface 2 RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wire | |
| Operating mode Semi-duplex | |
| File format/coding UART (11/10 bit switchable; NRZ) | |
| Data direction switching Automatic control, min. station response time 1 bits | |
| Transmission medium 2-wire twisted pair, shielded | |
| Transmission length ≤ 1200 m (depends on transmission speed, bus system and cable type) | |
| Cascadability 9 (4,8 ... 93,75 kbps) | |
| Conductor cross section flexible min. 0.2 mm² | |
| Conductor cross section flexible max. 2.5 mm² | |
| Conductor cross section flexible max. 2.5 mm² | |
| Conductor cross section AWG min. 24 | |
| Conductor cross section AWG max. 12 | |
| Protocols supported transparent protocol | |
| Serial transmission speed 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 75 / 93.75 / 115.2 / 136 / 187.5 / 375 / 500 / 1500 kbps | |
| Ambient conditions | |
| Ambient temperature (operation) -40°C ... 70°C | |
| Ambient temperature (storage/transport) -40°C ... 85°C | |
| Permissible humidity (operation) 10 % ... 95 % (non-condensing) | |
| Altitude 5000 m (For restrictions see manufacturer's declaration) | |
| Degree of protection IP20 | |
| Noise immunity EN 50 082-2 | |
| General | |
| Electrical isolation VCC // RS-485 (A) // RS-485 (B) | |
| Test voltage data interface/power supply 1.5 kVrms (50 Hz, 1 min.) | |
| Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU | |
| Net weight 188.8 g | |
| Housing material PA 6.6-FR | |
| Color green | |
| MTTF 1808 Years (SN 29500 standard, temperature 25°C, operating cycle 21 % (5 days a week, 8 hours a day)) 796 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25 % (5 days a week, 12 hours a day)) 334 Years (SN 29500 standard, temperature 40°C, operating cycle 100 % (7 days a week, 24 hours a day)) | |
| Conformance CE-compliant | |
| ATEX II 3 G Ex nA IIC T4 Gc (Please follow the special installation instructions in the documentation!) | |
| UL, USA/Canada 508 recognized | |
| Noise emission EN 50 081-1 | |
| Transmission channels 2 (1/1), TD, RD, half duplex | |
| Bit delay < 200 ns | |
| Bit distortion <1.5 % | |
| Test voltage data interfaces 1.5 kV AC | |
| Test voltage data interface/power supply 1.5 kV AC | |
| Degree of pollution 2 | |
| IECEx Ex nA IIC T4 Gc | |
| Bit distortion, input max. ± 35 % | |
| Bit distortion, output <3.6 % | |
| Power supply | |
| Nominal supply voltage 24 V AC/DC | |
| Supply voltage range 18 V AC/DC ... 30 V AC/DC (via pluggable COMBICON screw terminal block) | |
| Typical current consumption 90 mA (24 V DC) | |
| Max. current consumption 100 mA | |
| Conductor cross section flexible max. 2.50 mm² | |
| Conductor cross section flexible min. 0.20 mm² | |
| Conductor cross section solid max. 2.50 mm² | |
| Conductor cross section solid min. 0.20 mm² | |
| Max. AWG conductor cross section, flexible 12 | |
| Min. AWG conductor cross section, flexible 24 | |
| Conductor cross section AWG max. 12 | |
| Conductor cross section AWG min. 24 | |
| Dimensions | |
| Width 22.5 mm | |
| Height 99 mm | |
| Depth 114.5 mm | |
| Environmental Product Compliance | |
| China RoHS Environmentally Friendly Use Period = 50 | |
| Standards and Regulations | |
| Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU | |
| Free fall In acc. with IEC 60068-2-32 Result: 1 m | |
| Vibration resistance In acc. with EN 60068-2-6/IEC 60068-2-6 Result: 5g, 10...150 Hz, 2.5 h, in XYZ direction | |
| EMC Immunity EN 61000-4-2: Contact discharge ± 6 kV (Test Level 3) EN 61000-4-3: Frequency range 26 MHz ... 3 GHz (Test Level 3) EN 61000-4-4: Criterion B EN 61000-4-5: Signal ± 1 kV (Data line, asymmetrical) EN 55011 EN 61000-4-6: Frequency range 0.15 MHz ... 80 MHz | |
| Conformance CE-compliant | |
| ATEX II 3 G Ex nA IIC T4 Gc | |
| UL, USA/Canada 508 recognized | |
| Noise emission EN 50 081-1 | |
| Noise immunity EN 50 082-2 | |
| Shock In acc. with EN 60068-2-27/IEC 60068-2-27 Result: 25g, 11 ms period, half-sine shock pulse | |
| Connection in acc. with standard CUL | |
| IECEx Ex nA IIC T4 Gc | |
| UL, USA/Canada Class I, Div. 2, Groups A, B, C, D Class I, Zone 2, AEx nA IIC T4 Class I, Zone 2, Ex nA IIC T4 Gc X | |
| Approvals | |
| UL Recognized cUL Recognized DNV EAC KC cULus Recognized UL Listed cUL Listed IECEx ATEX cULus Listed | |
| Commercial data | |
| Packing unit 1 | |
| Weight per piece 202.0 g | |
| Country of origin Germany |