PSI-MODEM-SHDSL/SERIAL Copper Extender

The PSI-MODEM-SHDSL/SERIAL to Copper Extender transparently extends serial data transmission up to 20 km [12.4 mi] across single twisted pair (CAT5/6/7), coax or any existing copper wiring previously used in alarm circuits, E1/T1 circuits, CCTV and CATV applications.

SHDSL is the technologyof choice for the transmission of digitaldata over long distance copper wiresof a network. Although performance depends on the characteristics of the cable used, the reach of SHDSL is much further than any other DSL technology currently available. In addition, upload and download bandwidth is symmetrical boasting data rates as high as15.3 Mbps over 2-wire copperand30 Mbps over 4-wire copper.

The PSI-MODEM-SHDSL/SERIAL to Copper Extender isprotocol transparentand supportsRS-232, RS-422 and RS-485interfaces. With two SHDSL ports you can easily set up point-to-point, redundant point-to-point, linear and star topology networks.

The PSI-MODEM-SHDSL/SERIAL to Copper Extender transparently extends serial data transmission up to 20 km [12.4 mi] across single twisted pair (CAT5/6/7), coax or any existing copper wiring previously used in alarm circuits, E1/T1 circuits, CCTV and CATV applications.

SHDSL is the technologyof choice for the transmission of digitaldata over long distance copper wiresof a network. Although performance depends on the characteristics of the cable used, the reach of SHDSL is much further than any other DSL technology currently available. In addition, upload and download bandwidth is symmetrical boasting data rates as high as15.3 Mbps over 2-wire copperand30 Mbps over 4-wire copper.

The PSI-MODEM-SHDSL/SERIAL to Copper Extender isprotocol transparentand supportsRS-232, RS-422 and RS-485interfaces. With two SHDSL ports you can easily set up point-to-point, redundant point-to-point, linear and star topology networks.

Specifications
1 Year Return to Factory Warranty Reach, RoHS and WEEE Compliant HTSUS Number: 8517.62.0020 UNSPSC Code: 43222608 ECCN: 5A991
Serial interface
Interface 1 V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN 66259-1
Interface RS-232
Connection method D-SUB 9 plug
Transmission length max. 15 m
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 13
Data flow control/protocols Software handshake, Xon/Xoff, hardware handshake (RTS/CTS), 3964R-compatible, Modbus (RTU/ASCII), transparent protocol - additional protocols supported
Serial transmission speed 0.11/0.3/1.2/2.4/4.8/9.6/19.2/38.4/57.6/115.2/230.4 kbps, NRZ
Interface 2 SHDSL interface according to ITU-T G.991.2.bis
Connection method 2 x 2-pos. COMBICON plug-in screw terminal blocks
Transmission length up to 20 km (Depending on data rate and cable cross section)
Serial transmission speed 4-wire operation: 64 kbps ... 30 Mbps 2-wire operation: 32 kbps ... 15.3 Mbps
Interface 3 USB 2.0
Connection method Mini-USB type B, 5-pos.
Transmission length <5 m (only for configuration and diagnostics)
Interface 4 RS-422 interface in acc. with ITU-T V.11, EIA/TIA-422, DIN 66348-1
Interface RS-422
Connection method Plug-in/screw connection via COMBICON
File format/coding Serial asynchronous UART/NRZ, 7/8 data bits, 1/2 stop bits, 1 parity bit (even, odd, mark, space, none), 9/10/11-bit character length
Transmission length ≤ 1200 m
Termination resistor 390 Ω - 180 Ω - 390 Ω (can be connected)
Data flow control/protocols Automatic control // Modbus RTU/ASCII
Serial transmission speed 1.2/2.4/4.8/7.0/9.6/19.2/38.4/57.6/75/93.75/115.2/136/187.5/375/500/1500/2000 kbps, NRZ
Interface 5 RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wire
Interface RS-485
Connection method Plug-in/screw connection via COMBICON
File format/coding Serial asynchronous UART/NRZ, 7/8 data, 1/2 stop, 1 parity, 10/11-bit character length
Transmission length up to 1200 m
Termination resistor 390 Ω - 180 Ω - 390 Ω (can be connected)
Protocols supported Transparent, including 3964R protocol
Data flow control/protocols Automatic control // Modbus RTU/ASCII
Serial transmission speed 1.2/2.4/4.8/7.0/9.6/19.2/38.4/57.6/75/93.75/115.2/136/187.5/375/500/1500/2000 kbps, NRZ
Digital outputs
Output name Digital output
Number of outputs 2
Voltage output signal depending on the operating voltage
Current output signal ≤ 150 mA (Short-circuit-proof)
Behavior of the outputs Deactivated for device supply via DIN rail connector
Function
Management User-friendly software: Guided configuration, plausibility checks, diagnostic functions, log book
Status and diagnostic indicators LEDs: VCC (supply voltage), RD/TD (serial data traffic), ERR (errors), TERM (termination resistor active), RS-232 (RS-232 active)
2 x LINK / 2 x STAT (DSL data traffic port A and port B), DIAG (diagnostic messages)
Ambient conditions
Ambient temperature (operation) -20°C ... 60°C (for derating, see technical documentation)
Ambient temperature (storage/transport) -40°C ... 85°C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Altitude 5000 m (For restrictions see manufacturer's declaration)
Degree of protection IP20
Noise immunity EN 61000-6-2
General
Electrical isolation DIN EN 50178 (VCC, RS-232 // RS-422, RS-485 // DSL (A) // DSL (B) // FE)
Test voltage data interface/power supply 1.5 kVrms (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Net weight 339.4 g
Housing material PA 6.6-FR
Color green
MTTF 693 Years (SN 29500 standard, temperature 25°C, operating cycle 21 % (5 days a week, 8 hours a day)) 301 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25 % (5 days a week, 12 hours a day)) 121 Years (SN 29500 standard, temperature 40°C, operating cycle 100 % (7 days a week, 24 hours a day))
Conformance CE-compliant
Noise emission EN 55011
MTBF 1004 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 199 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
Power supply
Nominal supply voltage 24 V DC ±5 % (as an alternative or redundant, via backplane bus contact and system current supply) 5 V DC (configuration only, via mini-USB type B)
Supply voltage range 18 V DC ... 30 V DC
Typical current consumption <180 mA (24 V DC)
Connection method COMBICON plug-in screw terminal block
Dimensions
Width 35 mm
Height 99 mm
Depth 114.5 mm
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Conformance CE-compliant
ATEX II 3 G Ex nA nC IIC T4 Gc X
UL, USA/Canada cULus listed UL 508
Shock 15g in all directions in acc. with IEC 60068-2-27
Noise emission EN 55011
Noise immunity EN 61000-6-2
Vibration (operation) In acc. with IEC 60068-2-6: 5g, 150 Hz
Approvals
UL Listed cUL Listed EAC ATEX cULus Listed
Commercial data
Packing unit 1
Weight per piece 360.0 g
Country of origin Germany